3 f 4W, 3 f 3W, 3 f Balanced, 1 f 2W, and 1 f 3W Power Measurement. AC+DC true power, and True RMS AC Voltage and Current AC+DC 2000A, AC 600V, DC 800V AC+DC 1200KW(1 f ), AC+DC 2000KW (3 f ) Dual Display V+Hz, A+Hz, W+PF, KVA+KVAR, V+A Phase Angle Measurement 3 f RST(L1L2L3) Sequence Indication. Memory of 4 records. DCA/DCW Auto Zero when power clamp powering on. AC/DC Auto Detection. Auto range.
AC+DC True Power (PF 0.2-1.0, 3 Φ 3W, 3 Φ 4W, 1 Φ 2W, and 1 Φ 3W)
Range
Resolution
Accuracy(of rdg)
Input Range
0-99.9KW
0.1KW
+/- 2.0% +/- 0.05KW
AC 600V, DC 800V, ACA/DCA 2000A
100-999.9KW
0.1KW
+/- 2.0% +/- 0.5KW
AC 600V, DC 800V, ACA/DCA 2000A
1000-1200KW
1KW
+/- 2.0% +/- 5KW
AC 600V, DC 800V, ACA/DCA 2000A
AC+DC True Power (Power Factor 0.2-1.0, 3 Φ Balanced Power)
Range
Resolution
Accuracy(or rdg)
Input Range
0-99.99KW
0.01KW
+/- 2.0% +/- 0.5KW
AC 600V, DC 800V, ACA/DCA 2000A
100-999.9KW
0.1KW
+/- 2.0% +/- 0.5KW
AC 600V, DC 800V, ACA/DCA 2000A
1000-1200KW
1KW
+/- 2.0% +/- 5KW
AC 600V, DC 800V, ACA/DCA 2000A
POWER FACTOR (PF) PF=KW/KVA
AC+DC Voltage (True RMS, Crest Factor<4, Autorange, Overload Protection 800VAC for all ranges)
Range
Resolution
Accuracy(of reading)
Input Impedance
DC, 50/60Hz
40-400Hz
0-200A
0.1V
+/- 1.5% +/- 5 dgts
+/- 2.0% +/- 5 dgts
10M Ω
200-500A
0.1V
+/- 1.5% +/- 5 dgts
+/- 2.0% +/- 5 dgts
10M Ω
500-600VAC 500-800VDC
1V
+/- 1.5% +/- 5 dgts
+/- 2.0% +/- 5 dgts
10M Ω
AC+DC Current (True RMS, Crest Factor<4)
Range
Resolution
Accuracy(of reading)
Overload Protection
DC, 50/60 Hz
40-400Hz
0-200A
0.1A
+/- 1.5% +/- 5 dgts
+/- 2.0% +/- 5 dgts
AC 3000A
200-500A
0.1A
+/- 2.0% +/- 5 dgts
+/- 2.5% +/- 5 dgts
AC 3000A
500-2000A
1A
+/- 2.5% +/- 5 dgts
+/- 3.0% +/- 5 dgts
AC 3000A
AC+DC KVA (Apparent Power)
(KVA)=VxA/1000
AC+DC KVAR(Reactive Power)
(KVAR)=
Phase Angle (must zero current reading before measurement)