PROVA-5601/PROVA-5637 Clamp-on Ground Resistance Tester |
|
Non-Contact Ground Resistance Measurement No Auxiliary Electrode Needed Jaw Diameter Φ 23 mm (5601) Jaw Diameter Φ 35 mm(5637) 0.025 – 1500 Ohm 0.2mA– 30A(5601)0.2mA– 35A(5637),True RMS 116 Sets of Memory(5601,5637) Programmable Hi and Lo Alarm(5601,5637) Programmable Data Logging (5601,5637) APPLICTIONS Telecommunication Cable TV system Electrical Power Plant Cellular Phone System Factory and Facility Gas Station Tank
|
|
|
|
Ground Resistance (Auto range) |
Range |
Resolution |
Accuracy of Reading 1,2 |
0.025 - 0.250 W |
0.002 W |
± 1.5% ± 0.02 W |
0.250 - 1.000 W |
0.02 W |
± 1.5% ± 0.02 W |
1.001 - 9.999 W |
0.02 W |
± 1.5% ± 0.1 W |
10.00 - 50.00 W |
0.04 W |
± 1.5% ± 0.1 W |
50.01 - 99.99 W |
0.04 W |
± 1.5% ± 0.5 W |
100.0 - 200.0 W |
0.4 W |
± 3.0% ± 1.0 W |
200.1 - 400.0 W |
2 W |
± 5.0% ± 5 W |
400.1 - 600.0 W |
5 W |
± 10% ± 10 W |
600.1 - 1500 W |
20 W |
± 20% |
1 Loop resistance noninductive, external field < 200 A/m, external electrical field < 1 V/m, conductor centered.
2 Resistance Measurement Frequency: 1.667KHz,3.333KHz(optional) | |
Ground/Leakage Current (Auto range, 50/60 Hz, True RMS, Crest Factor < 3.5) |
Range |
Resolution |
Accuracy of Reading |
0.200 - 1.000 mA |
0.001 mA |
± 2.0% ± 0.05 mA |
1.00 - 10.00 mA |
0.01 mA |
± 2.0% ± 0.03 mA |
10.0 - 100.0 mA |
0.1 mA |
± 2.0% ± 0.3 mA |
100 - 1000 mA |
1 mA |
± 2.0% ± 3 mA |
0.20 - 35.00 A(5637) |
0.01A |
± 2.0% ± 0.03A |
0.20 - 15.00 A(5601) |
0.01A |
± 2.0% ± 0.03A |
0.20 - 30.00 A(5601) |
0.01A |
± 3.0% ± 0.03A | |
Accuracy of Resistance Calibration Plate |
±0.5% |
Data Logging Capacity |
116 records |
Data Logging Interval |
1 to 255 seconds |
Conductor Size |
35mm /1.38”(5637), 23mm /0.90”(5600,5601) |
Jaw Opening |
38mm /1.49”(5637), 27mm /1.06”(5600,5601) |
Battery Type |
9V IEC 6 LR61 (Alkaline) |
Display Type |
4 digits 9999 counts LCD |
Overload Indication |
OL |
Battery Life |
3000 measurements |
Low Battery Indication |
|
Range Selection |
Auto |
Power Consumption |
40mA |
Sampling Time |
0.5 seconds |
Operating Temperature |
0 ℃ to 50 ℃ (14 ℉ to 122 ℉ ) Operating Humidity: Less than 85% RH |
Storage Temperature |
-20 ℃ to 60 ℃ (-4 ℉ to 122 ℉ ) Storage Humidity: Less than 75% RH |
Dimension( 5637 |
276mm (L) x 100mm(W) x 47mm(H),10.8" (L) x 3.9"(W) x 1.9"(H) |
Dimension( 5600,5601 ) |
257mm (L) x 100mm(W) x 47mm(H),10.1" (L) x 3.9"(W) x 1.9"(H) |
Weight( 5637) |
750g/1.65lbs |
Weight( 5600,5601) |
640g/1.41lbs |
Accessories |
- Resistance Calibration Plate x 1
- Battery 9V (Installed) x 1
- Carrying Box x 1
- Users Manual x 1
| | |
|
LANGUAGUE |
|
| |