Display of Overlapped Voltage and Current Waveform Maximum Demand(MD in W,KW,MW) with Programable Period Harmonics Analysis ( V and I ) to the 50th Order Display of 25 Harmonics in One Screen with Waveform Display of waveform with Peak Values (512 Samples / Period), Datalogging of 32, 64, 128 or 256 Points/Cycles Analysis of Total Harmonics Distortion ( % THD-F ) Graphic Phasor Diagram Programmable PT (1 to 3000) Ratios Capture 128 Transient Events ( Time + Cycles + Faults ) with Programmable Threshold(%), Can Also be Reviewed in LCD 50000 Records with Programmable Lnterval ( 1 to 6000 seconds) Output of Waveform, Power Parameters and 50 Harmonics at Command. Large Dot Matrix LCD Display with Backlight Optical Isolated RS-232C Interface Smart Datalogging to save Battery Power for Long-term Monitoring Built - in Calendar Clock for Data Logging
AC Watt ( 45 ~ 65 Hz, PF 0.5 to 1 , CT=1 )
Range
Resolution
Accuracy of Readings
100.0 - 999.9 W
0.1 W
2% ± 8 dgts
1.000 - 9.999 KW
0.001 KW
2% ± 8 dgts
10.00 - 99.99 KW
0.01 KW
2% ± 8 dgts
100.0 - 999.9 KW
0.1 KW
2% ± 8 dgts
1000 - 9999KW
1 KW
2% ± 8 dgts
AC Current (45~65 Hz , True RMS)
Range
Range
Resolution
Accuracy of Readings
30 - 300 A
0.00 - 300 A
0.1 A
1 % of range ± 8 dgts
300 - 999.9 A
100.0 - 999.9 A
0.1 A
1 % of range ± 8 dgts
1000 - 3000 A
1000 - 3000 A
1 A
1 % of range ± 8 dgts
Harmonics of ACA in % and Magnitude (1 to 50th order)
Range
Resolution
Accuracy in %
Resolution
Accuracy in Magnitude
10.0 - 300 A
0.1 %
±1.0%
0.1 A
±1.0% of range ± 0.8A
1000 - 3000 A
0.1 %
±1.0%
1 A
±1.0% of range ± 3 A
Power Factor (PF)
Range
Resolution
Accuracy of Readings
0.00 - 1.00
0.01
± 1.5 % ± 8 digits
Harmonics of AC Voltage in % and Magnitude (1 to 50th order)
Range
Resolution
Accuracy in %
Resolution
Accuracy in Magnitude
50 - 600 V
0.1 %
±0.5%
0.1V
±0.5 % ± 0.5V
Phase Angle ( Φ )
Range
Resolution
Accuracy of Readings
-180 ° to 180 ° (0 ° to 360 ° )
0.1 °
± 1 % ± 2 digits
AC Voltage ( 45 ~ 65 Hz, True RMS)
Range
Resolution
Accuracy of Readings
3 V - 600 V
0.1 V
± 0.5 % ± 5 dgts
Total Harmonics Distortion (% THD-F , 1 to 50th order)
Range
Resolution
Accuracy of Readings
0.0 - 999.9 %
0.1 %
± 0.5 % ± 5 digits
General Specification:
Conductor Size
150 mm (approx.)
Battery Type
1.5 V SUM-3 *2
Display
128*64 Dot Matrix
Power Consumption
10 mA (approx.)
Auto - Power - Off
15 minutes
LCD update rate
2 times/sec
Dimension
130mm(L)*80mm(W)*43mm(H),5.1"(L)*3.1"(W)*1.7"(H)
Accessories
Test lead*1 pair, Users ,anual*1, Batteries 1.5V*2