Electrical Specifications: (23℃±3℃, 50/60Hz, conductor located at the center of the flexible loop) Sliding Switch Position | 300A AC | 3000A AC | Range | 3 – 300A | 30 – 3000A | Output Select | 300mV | 1V | 300mV | 1V | Output Signal | 1mV/A | 3.33mV/A | 0.1mV/A | 0.333mV/A | Accuracy | 1% of full scale | 1% of full scale | Linearity (10 to 100%) | 0.2% of reading | 0.2% of reading | Position Sensitivity | 2% of full scale | 2% of full scale | External Field (200 mm from the head, < 40A/m) | 1% of full scale | 1% of full scale | Phase Error | < ± 1˚ | < ±1˚ | Temperature Coefficient ( 0 to 70˚C) | 0.02% of reading / ˚C | 0.02% of reading / ˚C |
Sliding Switch Position | 30A AC | Range | 3 – 30A | Output Select | 300mV | 1V | Output Signal | 10mV/A | 33.3mV/A | Accuracy | 3% of full scale | Linearity (10 to 100%) | 0.2% of reading | Position Sensitivity | 3% of full scale | External Field (200 mm from the head, < 40A/m) | 1% of full scale | Phase Error | < ± 2˚ | Temperature Coefficient ( 0 to 70˚C) | 0.02% of reading / ˚C |
DC offset: < 20mVDC (300A AC range) < 100mVDC (30A AC range) < 20mVDC (3000A AC range) Noise: < 2mACVRMS Bandwidth (-3dB): 10 to 10 KHz Load Impedance: 1KΩ General Specifications: Probe Length: 3000-24 | 24 in / 610 mm | Minimum Bending Diameter: | 35mm | Connector Diameter: | 23mm | Cable Diameter: | 14mm | Cable Length from Probe to Box: | 1700mm | Cable Length from Box to Output: | 1700mm | Dimension (Box): | 130mm(L) x 80mm(W)x 43mm(H) 5.1”(L) x 3.1”(W) x 1.7”(H) | Battery Type: | two 1.5V SUM-3 (Alkaline, 2000mAHrs) | Battery Life: | 300 Hours | Operating Temperature: | -10°C to 85°C | Operating Humidity: | 15% to 85% RH | Altitude: | up to 2000M | Storage Temperature: | -20°C to 85°C | Storage Humidity: | 15% to 85% RH | Weight: | 430g (battery included) | Accessories: | Carrying case x 1 Users manual x 1 Batteries 1.5V x 2 |
|