PROVA-6830+6801 Power and Harmonics Analyzer (100A)
Analysis for 3P4W, 3P3W, 1P2W, 1P3W True RMS Value(V 123 and L 123 ) Active Power(W, KW, MW, GW) Apparent and Reactive Power (KVA, KVAR) Power Factor (PF), Phase Angle (Φ) Energy (WH, KWH, KVARH, PFH) Current Measurement from 0.1mA to 3000A, Capable of Analyzing IT Standby Power Consumption to the Maximum Demand of a Factory Display of 35 Parameters in One Screen(3P4W) rogrammable CT (1 to 600) and PT (1 to 3000) Ratios Display of Overlapped Voltage and Current Waveform 2.4M Memory with Programmable Interval (1 to 6000 seconds, 17000 Records for 3P4W System) Output of Waveform, Power Parameters and Harmonics at Command Large Dot Matrix LCD Display with Backlight Average Demand (AD in W, KW, MW) aximum Demand (MD in W, KW, MW) with Programmable Period Harmonic Analysis to the 99th Order Display of 50 Harmonics in One Screen with Waveform Display of Waveform with Peak Values (1024 Samples/Period) Analysis of Total Harmonic Distortion (%THD-F) Graphic Phasor Diagram with 3 Phase System Parameters Capture 28 Transient Events (Time+Cycles) with Programmable Threshold(%) 3 Phase Voltage Unbalance Ratio (VUR) 3 Phase Voltage Unbalance Factor (d0%, d2%) Calculated Unbalance Current through Neutral Line (In) Optical isolated USB Interface Built-in Timer and Calendar for Data Logging onductor Size: -Model 6801 30mm(approx) -Model 6802 5 55mm(approx),64*24mm(bus bar) -Model 3007 170mm(approx)
* Please refer to users manual for more detailed and up-to-date description of specification
AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1)
Range
Resolution
Accuracy of Readings
6800+6801
6800+6802
6800+3007
5.0 – 999.9W
0.1W
±1% ± 8dgts
±1% ± 8dgts
±1% of VA Range ±8dgts
1.000 – 9.999 KW
0.001 KW
±1% ± 8 dgts
±1% ± 8 dgts
±1% of VA Range ±8dgts
10.00 – 99.99 KW
0.01 KW
±1% ± 8 dgts
±1% ± 8 dgts
±1% of VA Range ±8dgts
100.0 – 999.9 KW
0.1 KW
±1% ± 8dgts
±1% ± 8dgts
±1% of VA Range ±8dgts
1000 – 9999 KW
1 KW
±1% ± 8dgts
±1% ± 8dgts
±1% of VA Range ±8dgts
0.000 – 9.999MW
0.001MW
–
±1% ± 8 dgts
±1% of VA Range ±8dgts
AC Current( 50 or 60Hz, Auto Range,True RMS,Crest Factor<4,CT=1)
Range
Resolution
Accuracy of Readings
6800+6801
(Overload Protection AC200A)
0.050 – 9.999A
0.001A
±0.5% ± 5dgts
10.00 – 60.00A
0.01A
±0.5% ± 5dgts
60.00 – 99.99A
0.01A
±1.0% ± 5dgts
6800+6802
(Overload Protection AC2000A)
0.04 – 10.00A
0.01A
–
0.4A – 100.0A
0.1A
±0.5% ± 5dgts
4.0 – 1000.0A
1A
±0.5% ± 5dgts
6800+ 3007
(Overload Protection AC3500A)
4 – 300A
0.1A
±1% of Range ±5dgts
300.0 – 999.9A
0.1A
±1% of Range ±5dgts
1000 – 3000A
1A
±1% of Range ±5dgts
AC Voltage (50 or 60 Hz, Auto Range, True RMS, Crest FActor<4)
Range
Resolution
Accuracy of Readings
Range
Resolution
Accuracy of Readings
4.0V – 500.0 (Phase to Neutral)
0.1V
± 0.5% ± 5dgts
4.0V –600.0V (Phase to phase)
0.1V
± 0.5% ± 5dgts
Harmonics of AC Voltage in % and in Magnitude (1 to 99th order, minimum voltage at the 50 or 60 Hz>AC 80V)
Range
In Percentage
In Magnitude
Resolution
Accuracy of readings
Resolution
Accuracy of readings
1 – 20 th
0.1%
±2%
0.1 V
±2% ±0.5V
21 – 49 th
4% of reading ±2.0%
4% of reading ±0.5A
50 – 99 th
6% of reading ±2.0%
6% of reading ±0.5A
Harmonics of AC Current in % and in Magnitude
Model 6800+6801(100A)(1 to 99th order, minimum current at 50 or 60 Hz is greater than 10% of the range)
Range
In Percentage
In magnitude
Resolution
Accuracy of reading
Resolution
Accuracy of reading
1 – 10 th
0.1%
±0.2 of reading ±1%
0.1mA / 0.1A
±0.2% of reading ±7dgts
11 – 20 th
±2% of reading ±1%
±2% of reading ±7dgts
2 1 – 50 th (A range)
±5% of reading ±1%
±5% of reading ±7dgts
2 1 – 50 th (mA range)
±10% of reading ±1%
±10% of reading ±7dgts
5 1 – 99 th
±35% of reading ±1%
±35% of reading ±7dgts
Model 6800+6802(1000A);6800+3007(3000A)(1 to 99th order, minimum current at the 50 or 60 Hz>20A)
Range
In Percentage
In Magnitude
Resolution
Accuracy of reading
Resolution
Accuracy of reading
1 – 20 th
0.1%
±2%
0.1A(6802) / 0.3A(3007)
±2% of reading ±0.4A/0.6A
21 – 49 th
4% of reading ±2.0%
±4% of reading ± 0.4A/0.6A
50 – 99 th
6% of reading ±2.0%
±6% of reading ± 0.4A/0.6A
Total Harmonic Distortion
Range
Resolution
Accuracy(6801)
Accuracy(6802)
Accuracy(3007)
0.0 – 20%
0.1%
±1%
±2%
±2%
20 – 100%
0.1%
±3% of reading ±5%
±6% of reading ±1%
±6% of Range ±1%
100 – 999.9%
0.1%
±10% of reading ±10%
±10% of reading ±1%
±10% of Range ±1%
Peak Value of Ac Voltage or AC Current ,VT=1
Range
Samping Time
Accuracy of reading
50Hz
39 μS
±5% ±30digits
60Hz
33 μS
±5% ±30 digits
Crest Factor (C.F.) of ACV or ACA ,VT=1
Range
Resolution
Accuracy of reading
1.00 – 99.99
0.01
±5% ±30digits
Frequency in AUTO mode
Range
Resolution
Accuracy of reading
45 – 65Hz
0.1Hz
0.1Hz
Power Factor (PF)
Range
Resolution
Accuracy of reading
0.00 – 1.00
0.01
± 0.04
Phase Angle (Φ)
Range
Resolution
Accuracy of reading
-180 。 to 180 。
0.1 。
± 1 。
Conductor Size (6801)
30mm (approx)
Conductor Size (6802)
55mm(approx.), 64 X 24mm(Bus Bar)
Conductor Size (3007)
170mm(approx)
Battery Type
1.5V SUM-3 x 8
Display
Dot Matrix LCD with backlight
Power Consumption
140mA (approx.)
External DC Input
DC 12V adaptor (for safety purpose, the adaptor must be certified with 600Visolation protection)
LCD update rate
1 times / sec
No. Of Samples/Period
1024
Operating Humidity
< 85% relative
Operating Temperature
-10°C to 50°C
Storage Humidity
< 75% relative
Storage Temperature
- 20°C to 60°C
Weight(6830)
1160g
Weight(6801)
200g
Weight(6802)
600g
Dimension(6830)
257 (L) x 155 (W) x 57 (H) mm ,10.1"(L) x 6.1" (W) x 2.3" (H)
Dimension(6801)
210 (L) x 62 (W) x 36 (H) mm ,8.3 " (L) x 2.5" (W) x 1.4" (H)
Dimension(6802)
244 (L) x 97 (W) x 46 (H) mm ,9.6 " (L) x 3.8" (W) x 1.8" (H)
Accessories
test leads x 4,alligator clips x 4,Carrying bag x 1,Users manual x 1,Batteries 1.5V x 8