PROVA-6830A+6802 Power and Harmonics Analyzer (1000A)
Power Analysis for 3P4W, 3P3W, 1P2W, 1P3W True RMS value (V123 and I123) Active Power (W, KW, MW, GW) Apparent and Reactive Power (KVA, KVAR) Power Factor (PF), Phase Angle (Φ) Energy (WH, KWH, KVARH, PFH) AC Current (0.04A to 6000A) and Voltage measurement: True RMS, Auto Range.
Power Analysis for 3P4W, 3P3W, 1P2W, 1P3W
True RMS value (V123 and I123)
Active Power (W, KW, MW, GW)
Apparent and Reactive Power (KVA, KVAR)
Power Factor (PF), Phase Angle (Φ)
Energy (WH, KWH, KVARH, PFH)
AC Current (0.04A to 6000A) and Voltage measurement: True RMS, Auto Range.
Capable of analyzing IT standby power consumption to the maximum demand of a factory
Display of 35 Parameters in One Screen (3P4W)
Programmable CT (1 to 600) and PT (1 to 3000) Ratios
Display of Overlapped Voltage and Current Waveform
Average Demand (AD in W, KW, MW)
Maximum Demand (MD in KW, MW, KVA, MVA) with Programmable Period
Harmonic Analysis to the 99th Order
Display of 50 Harmonics in one Screen with Waveform
Display of Waveform with Peak Values (1024 Samples / Period)
Analysis of Total Harmonic Distortion (THD-F)
Graphic Phasor Diagram with 3 Phase System Parameters
DIP, SWELL, and OUTAGE are included in transient events.
3 Phase Voltage or Current Unbalance Ratio (VUR, IUR)
3 Phase Voltage or Current Unbalance Factor (d0%, d2%)
Calculated Unbalanced Current through Neutral Line (In)
512K Memory with Programmable Interval (Sampling time from 2 to 3000 seconds, 17,000 records for 3P4W system)
Output of Waveform, Power Parameters and Harmonics at Command
Large Dot Matrix LCD Display with Backlight
Software to work with PC via Optical Isolated RS-232C to USB Interface
Built-in timer and calendar for data logging
Conductor Size: ■ Model 6801 (100A) 30mm(approx),210mm(L) x 62mm(W) x 36mm(H),200g(Weight) ■ Model 6802 (1000A) 55mm(approx),64*24mm(bus bar) 244mm (L) x 97mm(W) x 46mm(H),600g(Weight) ■ Model 3007 (3000A) 24in/610mm(Probe Length) 130mm(L) x 80mm(W) x 43mm(H),410g(Weight) ■ Model 3009 (1200A) 18in/460mm(Probe Length) 130mm(L) x 80mm(W) x 43mm(H),390g(Weight) ■ Model 3006(6000A) 130mm(L) x 80mm(W) x 43mm(H),430g(Weight)
PROVA-6830A + 6802 (1000A)
Electrical Specifications: (23℃±5℃)
AC Watt
Range (0 to 1000A)
Resolution
Accuracy of Readings
5.0 – 999.9 W
0.1W
±1% ± 0.8W
1.000 – 9.999 KW
0.001 KW
±1% ± 8W
10.00 – 99.99 KW
0.01 KW
±1% ± 80W
100.0 – 999.9 KW
0.1 KW
±1% ± 0.8KW
1000 – 9999 KW
1 KW
±1% ± 8KW
0.000 – 9.999MW
0.001MW
±1% ± 80KW
Range of CT (Current Transformer) Ratio: 1 to 600
AC Apparent Power (VA, from 0.000 VA to 9999 KVA): VA = V r.m.s. x A r.m.s
AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR): VAR = √(VA2 – W2)
AC Active Energy (mWH, WH, or KWH, from 0mWH to 999,999KWH):
WH = W * Time (in hours)
AC Current(Auto range, TRMS, Overload Protection AC 2000A)
Range
Resolution
Accuracy of Readings
10.00A
0.001A/0.01A
–
5A - 100.0A
0.01A/0.1A
±0.5% ± 0.5A
50A – 1000.0 A
0.1A/1 A
±0.5% ± 5A
AC Voltage(Auto range, TRMS, Overload Protection AC 800V)
Range
Resolution
Accuracy of Readings
20.0 V – 500.0 V (Phase to Neutral)
0.1 V
±0.5% ± 5dgts
20.0 V – 600.0 V (Phase to Phase)
Range of VT (Voltage Transformer) Ratio: 1 to 3000
Harmonics of AC Voltage in Percentage
Range
Resolution
Accuracy
1 – 20th
0.1%
±2%
21 – 49th
±4% of reading ± 2.0%
50 – 99th
±6% of reading ± 2.0%
Harmonics of AC Voltage in Magnitude
Range
Resolution
Accuracy
1 – 20th
0.1V
±2% ± 0.5V
21 – 49th
±4% of reading ± 0.5V
50 – 99th
±6% of reading ± 0.5V
Harmonics of AC Current in Percentage
Range
Resolution
Accuracy
1 – 20th
0.1 %
±2%
21 – 49th
±4% of reading ± 2.0%
50 – 99th
±6% of reading ± 2.0%
Harmonics of AC Current in Magnitude
Range
Resolution
Accuracy
1 – 20th
0.1A
±2% of reading ±0.4A
21 – 49th
±4% of reading ±0.4A
50 – 99th
±6% of reading ±0.4A
Power Factor(PF)
Range
Resolution
Accuracy
0.00 – 1.00
0.01
± 0.04
Phase Angle(Φ)
Range
Resolution
Accuracy
-180° to 180°
0.1°
± 1°
Peak Value of ACV (peak value > 20V) or ACA (peak value > 20A), VT=1
Range
Sampling Time
Accuracy of Reading
50 Hz
19μs
± 5% ± 30 digits
60 Hz
16μs
Crest Factor (C.F.) of ACV(peak value >20V)or ACA (peak value > 20A), VT=1
Range
Resolution
Accuracy of Readings
1.00 – 99.99
0.01
± 5% ± 30 digits
Frequencyin AUTO mode
Range
Resolution
Accuracy
45 – 65 Hz
0.1Hz
± 0.1Hz
Total Harmonic Distortion (THD-F)
Range
Resolution
Accuracy
0.0 – 20%
0.1%
± 2%
20 – 100%
± 6% of reading ± 1%
100 – 999.9 %
± 10% of reading ± 1%
General Specifications: Indoors Use
PROVA 6830A Analyzer
Battery Type:
1.5V SUM-3 x 8
External DC Input:
Use only power supply adapter
Model PHAPSA
Display:
Dot Matrix LCD (240x128) with backlight
LCD Update Rate:
1 time / second
Power Consumption:
140mA (approx.)
No. Of Samples:
1024 samples / period
Data Logging Files:
85
Max. File Capacity:
17474 records (3P4W, 3P3W)
26210 records (1P3W)
52420 records (1P2W)
4096 records (50 Harmonics / record)
Sampling Time:
2 to 3000 seconds for data logging
Low battery Indication:
Overload Indication:
OL
Operating Temperature:
-10°C to 50°C
Operating Humidity:
less than 85% relative
Storage Temperature:
-20°C to 60°C
Storage Humidity:
less than 75% relative
Dimension:
257 (L) x 155 (W) x 57 (H) mm
10.1” (L) x 6.1” (W) x 2.3” (H)
Weight:
1160g (Batteries included)
Accessories:
Probes (model 6802) x 3
Test leads (3 meter long) x 4
Alligator clips x 4
Carrying bag x 1
Users manual x 1
Batteries 1.5V x 8
AC power adapter x 1 Software CD x 1 Software users manual x 1 USB to RS232 cable x 1